JAMPTOC Output signals
Table 454: JAMPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
4.1.7.8 JAMPTOC Settings
Table 455: JAMPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Start value 0.10...10.00 xIn 0.01 2.50 Start value
Operate delay time 100...120000 ms 10 2000 Operate delay time
Table 456: JAMPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 100 Reset delay time
4.1.7.9 JAMPTOC Monitored data
Table 457: JAMPTOC Monitored data
Name
Type Values (Range) Unit Description
START BOOLEAN
0=False
1=True
Start
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
JAMPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.7.10 Technical data
Table 458: JAMPTOC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Reset time Typically 40 ms
Reset ratio Typically 0.96
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
401