ABB RELION REX640 - Faulted phase selection, the voltage-dependent overcurrent method

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start of element START_GFC STARTS_GF
C
RELEASE_P
E
RELEASE_P
P
I
B
> & I
C
>
TRUE BC Fault No fault BC Fault
I
C
> & I
A
>
TRUE CA Fault No fault CA Fault
I
A
> & I
B
> &
EARTH_FLT
TRUE AB Fault AB Fault AB Fault
I
B
> & I
C
> &
EARTH_FLT
TRUE BC Fault BC Fault BC Fault
I
C
> & I
A
> &
EARTH_FLT
TRUE CA Fault CA Fault CA Fault
I
A
> & I
B
> & I
C
4
TRUE ABC Fault No fault ABC Fault
I
A
> & I
B
> & I
C
> &
EARTH_FLT
5
TRUE ABC Fault ABC Fault ABC Fault
In case of a high-impedance earthed network, a phase preference logic can be
added to complement the phase selection in case of a cross-country fault. This can
affect the RELEASE_PE signals.
In case of a low-impedance earthed network, a faulted loop selection logic can be
added to complement the phase selection in case of a two-phase-to-earth fault.
This can affect the RELEASE_PE and RELEASE_PP signals.
Faulted phase selection, the voltage-dependent overcurrent method
The "Voltdep overcur" method combines the overcurrent and undervoltage
conditions. The phase current amplitude is compared to the
Str A Ph Sel GFC
threshold setting but a lower current
Lo A Ph Sel GFC
threshold is valid during
an undervoltage condition. This increases the sensitivity of the fault detection. The
amplitude of phase-to-earth and phase-to-phase voltages is compared to the
Ph V
Ph Sel GFC
and
PP V Ph Sel GFC
settings. In case of a three-phase fault, the phase-
to-phase voltages are monitored and compared to the
PP V Ph Sel GFC
setting.
Earth-fault recognition is always required to release a phase-to-earth
impedance-measuring element.
4
This applies to near three-phase faults. If voltages are still relatively high, all PP releases are
given.
5
This applies to near three-phase faults with EF indication. If voltages are still relatively high, all PE
and PP releases (except ABC Fault) are given.
1MRS759142 F Protection functions
REX640
Technical Manual
951