Parameter Values (Range) Unit Step Default Description
12=December
3.20.4.8 CALGAPC Monitored data
Table 218: CALGAPC Monitored data
Name Type Values (Range) Unit Description
CALGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
3.20.5 Time delay off, eight channels TOFGAPC (ANSI 62TOF)
3.20.5.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time delay off, eight channels TOFGAPC TOF 62TOF
3.20.5.2 Function block
Figure 135: Function block
3.20.5.3 Functionality
The time delay off, eight channels, function TOFGAPC can be used, for example,
for a drop-off-delayed output related to the input signal. The function contains
eight independent timers. There is a settable delay in the timer. Once the input is
activated, the output is set immediately. When the input is cleared, the output stays
on until the time set with the
Off delay time
setting has elapsed.
Basic functions
1MRS759142 F
244 REX640
Technical Manual