Name Type Values (Range) Unit Description
A Flt Phs B Magn FLOAT32 0.00...40.00 xIn Fault current phase B,
magnitude
A Flt Phs B angle FLOAT32 -180.00...180.00 deg Fault current phase B,
angle
A Flt Phs C Magn FLOAT32 0.00...40.00 xIn Fault current phase C,
magnitude
A Flt Phs C angle FLOAT32 -180.00...180.00 deg Fault current phase C,
angle
V Flt Phs A Magn FLOAT32 0.00...40.00 xUn Fault voltage phase A,
magnitude
V Flt Phs A angle FLOAT32 -180.00...180.00 deg Fault voltage phase A,
angle
V Flt Phs B Magn FLOAT32 0.00...40.00 xUn Fault voltage phase B,
magnitude
V Flt Phs B angle FLOAT32 -180.00...180.00 deg Fault voltage phase B,
angle
V Flt Phs C Magn FLOAT32 0.00...40.00 xUn Fault voltage phase C,
magnitude
V Flt Phs C angle FLOAT32 -180.00...180.00 deg Fault voltage phase C,
angle
5.7.11 Technical data
Table 1164: SCEFRFLO Technical data
Characteristic Value
Measurement accuracy
At the frequency f = f
n
Impedance:
±2.5 % or ±0.25 Ω
Distance:
±2.5 % or ±0.16 km/0.1 mile
XC0F_CALC:
±2.5 % or ±50 Ω
IFLT_PER_ILD:
±5 % or ±0.05
5.8 Switch-onto-fault protection CVPSOF (ANSI SOTF)
5.8.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Switch-onto-fault protection CVPSOF CVPSOF SOTF
Protection related functions 1MRS759142 F
1222 REX640
Technical Manual