Table 931: DSTPDIS Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
EF Cur stabilization
0=False
1=True
0=False EF current stabili-
zation enabled
Fact EF current Bal 1.000...2.000 0.001 1.200 Residual current ra-
tio for parallel line
compensation
Zone timer mode
1=Independent
2=Common
1=Independent Operate timer start
mode, zones
Voltage Mem time 0...300000 ms 10 40 Voltage memory
time
4.7.1.10 DSTPDIS Monitored data
Table 932: DSTPDIS Monitored data
Name Type Values (Range) Unit Description
STARTS_GFC Enum
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
Start signals for phases
A, B and C, GFC
RELEASE_PE Enum
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Release signals for PE-
loops, GFC
RELEASE_PP Enum
5=BC Fault
6=CA Fault
7=ABC Fault
4=AB Fault
-5=No fault
Release signals for
PP/3P loops, GFC
EARTH_FLT BOOLEAN
0=False
1=True
Indication of a single
phase earth-fault, GFC
DIR_E_FLT Enum
0=unknown
1=forward
2=backward
3=both
Earth-fault direction
(low imp. earthed), GFC
STARTS_Z1 INT32 -5...63 Start signals for phases
A, B and C, zone 1
STARTS_Z2 INT32 -5...63 Start signals for phases
A, B and C, zone 2
STARTS_Z3 INT32 -5...63 Start signals for phases
A, B and C, zone 3
Table continues on the next page