Name Type Values (Range) Unit Description
STARTS_Z4 INT32 -5...63 Start signals for phases
A, B and C, zone 4
STARTS_Z5 INT32 -5...63 Start signals for phases
A, B and C, zone 5
DIR_LOOP_R FLOAT32 -3000.00...3000.00 ohm Resistance used in dir.
evaluation, zone 1
DIR_LOOP_X FLOAT32 -3000.00...3000.00 ohm Reactance used in dir.
eval., zone 1
FLTLOOP_RFST FLOAT32 -3000.00...3000.00 ohm First PE-loop resist-
ance, zone 1
FLTLOOP_XFST FLOAT32 -3000.00...3000.00 ohm First PE-loop reactance,
zone 1
FLTLOOP_RSND FLOAT32 -3000.00...3000.00 ohm Second PE-loop resist-
ance, zone 1
FLTLOOP_XSND FLOAT32 -3000.00...3000.00 ohm Second PE-loop reac-
tance, zone 1
FLTLOOP_RPP FLOAT32 -3000.00...3000.00 ohm PP/3P-loop resistance,
zone 1
FLTLOOP_XPP FLOAT32 -3000.00...3000.00 ohm PP/3P-loop reactance,
zone 1
FLTPH_X FLOAT32 -3000.00...3000.00 ohm Phase to earth reac-
tance in phase domain,
zone 1
VMEM_USED BOOLEAN
0=False
1=True
Voltage memory in use
status
TLT_ANG_CONFLICT INT32 0...1023 Tilt angle conflict
DSTPDIS Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Time Timestamp Time
Release PE-loop Enum
-5=No fault
-4=ABCG Fault
-3=CAG Fault
-2=BCG Fault
-1=ABG Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Release signals for PE-
loops, GFC
Release PP-loop Enum
-5=No fault
-4=ABCG Fault
-3=CAG Fault
-2=BCG Fault
-1=ABG Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
Release signals for
PP/3P loops. GFC
Table continues on the next page
Protection functions 1MRS759142 F
996 REX640
Technical Manual