Name Type Values (Range) Unit Description
5=off
6.3.10.2 HZCCBSPVC Monitored data
Table 1267: HZCCBSPVC Monitored data
Name Type Values (Range) Unit Description
HZCCBSPVC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.3.10.3 HZCCCSPVC Monitored data
Table 1268: HZCCCSPVC Monitored data
Name Type Values (Range) Unit Description
HZCCCSPVC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.3.11 Technical data
Table 1269: HZCCxSPVC Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5 % of the set value or ±0.002 × I
n
Reset time <40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0 % of the set value or ±20 ms
6.4 Protection communication supervision PCSITPC
(ANSI PCS)
Supervision functions
1MRS759142 F
1326 REX640
Technical Manual