Distribution
Transformers
Medium and Large power transformers
Cooling mode ONAN ONAN ONAF OFAF ODAF
Constant K21 (k
21
) 1.00 1.00 1.00 1.00 1.00
Constant K22 (k
22
) 1.00 1.00 1.00 1.00 1.00
Oil Time Constant
(Շ
0
) [minutes]
180 210 150 90 90
Winding Tm Constant
(Շ
w
) [minutes]
4 10 7 7 7
A transformer is a distribution transformer if the
Transformer rating
setting < 2.5
MVA and
Transformer type
is set to "Three phase" or if the
Transformer rating
setting < 0.833 MVA and
Transformer type
is set to "Single phase".
Transformer parameters vary with the material used for winding and insulating
oil. The
Parameter Sel method
setting can be set to "Manual" and the constants
can be set individually through the
Oil exponent
,
Winding exponent
,
Constant K11
,
Constant K21
,
Constant K22
,
Oil time constant
and
Winding Tm constant
settings.
If
Parameter Sel method
is set to "Manual", the
Cooling mode
setting has
no effect on the transformer parameters.
Since there is no direct
Cooling mode
based time constants' selection
mentioned in the IEEE Std C57.91
™
- 2011 standard, the oil time constant
(Շ
0
) and winding time constant (Շ
w
) in
Table 1324
are kept same as in
Table 1323
.
For more accuracy, the values of the constants can be entered manually
by setting
Parameter Sel method
to "Manual".
7.3.5.2 Top oil temp calculation
The function receives two sensor inputs for measuring top oil temperature and
ambient temperature.
The top oil temperature of the tank is obtained through a sensor placed at
the upper inner turn of the winding. If the top oil temperature sensor status
TOIL_SNSFLT is FALSE, the top oil temperature is directly obtained from the
TOIL_TEMP input.
If the status of TOIL_SNSFLT is TRUE, indicating that the sensor is faulty, the top oil
temperature is calculated with the help of measured ambient temperature.
The status of the ambient temperature sensor is obtained through the AMB_SNSFLT
binary input. If AMB_SNSFLT is FALSE, indicating the healthy status of the sensor,
the ambient temperature is directly measured through the AMB_TEMP input. Else, if
AMB_SNSFLT is TRUE, the ambient temperature is taken from the
Average ambient
Tmp
setting.
The formula for calculating the top oil temperature from the measured or set
ambient temperature is shown in
Equation 322
.
Condition monitoring functions
1MRS759142 F
1386 REX640
Technical Manual