until the 10 minute time-out has passed or until the emergency start is released,
whichever takes longer.
The last change of the emergency start output signal is recorded.
5.6.7 Signals
5.6.7.1 ESMGAPC Input signals
Table 1140: ESMGAPC Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ST_EMERG_RQ BOOLEAN 0=False Emergency start in-
put
5.6.7.2 ESMGAPC Output signals
Table 1141: ESMGAPC Output signals
Name Type Description
ST_EMERG_ENA BOOLEAN Emergency start
5.6.8 ESMGAPC Settings
Table 1142: ESMGAPC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Motor standstill A 0.01...0.20 xIn 0.01 0.12 Current limit to
check for motor
standstill condition
Table 1143: ESMGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
5.6.9 ESMGAPC Monitored data
Protection related functions 1MRS759142 F
1192 REX640