3.19.11 Binary command to 32-bit integer conversion T_BIN_TCMD
3.19.11.1 Function block
Figure 112: Function block
3.19.11.2 Functionality
The binary command to 32-bit integer conversion function T_BIN_TCMD is used to
convert boolean input signals to 32 bit integer output signals.
Table 177: Conversion from Boolean to integer
RAISE LOWER OUT
FALSE FALSE 0
FALSE TRUE 1
TRUE FALSE 2
3.19.11.3 Signals
Table 178: T_BIN_TCMD input signals
Name Type Default Description
RAISE BOOLEAN 0 Raise command
LOWER BOOLEAN 0 Lower command
Table 179: T_BIN_TCMD output signals
Name Type Description
OUT INT32 Output signal