t0 t1+dt t2 t3 t5+dt
dt = Off delay time
t1 t4 t5
Figure 136: Timer operation
3.20.5.4 Signals
Table 219: TOFGAPC Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1 status
IN2 BOOLEAN 0=False Input 2 status
IN3 BOOLEAN 0=False Input 3 status
IN4 BOOLEAN 0=False Input 4 status
IN5 BOOLEAN 0=False Input 5 status
IN6 BOOLEAN 0=False Input 6 status
IN7 BOOLEAN 0=False Input 7 status
IN8 BOOLEAN 0=False Input 8 status
Table 220: TOFGAPC Output signals
Name Type Description
Q1 BOOLEAN Output 1 status
Q2 BOOLEAN Output 2 status
Q3 BOOLEAN Output 3 status
Q4 BOOLEAN Output 4 status
Q5 BOOLEAN Output 5 status
Q6 BOOLEAN Output 6 status
Q7 BOOLEAN Output 7 status
Q8 BOOLEAN Output 8 status
3.20.5.5 Settings
Table 221: TOFGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Off delay time 1 0...3600000 ms 1 0 Off delay time
Off delay time 2 0...3600000 ms 1 0 Off delay time
Off delay time 3 0...3600000 ms 1 0 Off delay time
Off delay time 4 0...3600000 ms 1 0 Off delay time
Off delay time 5 0...3600000 ms 1 0 Off delay time
Table continues on the next page
1MRS759142 F Basic functions
REX640
Technical Manual
245