11.8 Test mode
11.8.1 Functionality
The mode of all the logical nodes in the relay's IEC 61850 data model can be
set with
Test mode
.
Test mode
activation method can be changed via parameter
Configuration> System> Test mode selection. Available activation methods
are "Local", "Local+remote, maintenance", "Local+Remote, all levels" and "Binary
input". By default,
Test mode
activation method is "Local" which means the test
mode can be activated only via LHMI through parameter Tests> IED test>
Test mode. The remote activation method via binary input or via IEC 61850
communication is possible (LD0.LLN0.Mod). When the binary input is selected
as the test mode activation method, the behavior can be configured with the
application configuration.
Table 1656: Test mode
Test mode Description Protection
BEH_BLK
Protection
BEH_TST
Normal mode Normal operation FALSE FALSE
IED blocked Protection working as in “Normal
mode” but ACT configuration can
be used to block physical outputs
to process. Control function com-
mands blocked.
TRUE FALSE
IED test Protection works as in “Normal
mode” but protection functions
work in parallel with test parame-
ters
FALSE TRUE
IED test and
blocked
Protection works as in “Normal
mode” but protection functions
work in parallel with the test pa-
rameter. The ACT configuration can
be used to block physical outputs
to process. The control function
command is blocked.
TRUE TRUE
See function block Protection for more details.
The behavior data objects in all logical nodes follow LD0.LLN0.Mod value.
If "Normal mode" is selected, the behavior data objects follow the mode
(.Mod) data object of the corresponding logical device.
Vertical and horizontal communication is not blocked by the “IED
blocked” or “IED test and blocked” modes.
11.8.2 Application configuration and Test mode
The breaker and disconnector outputs from control commands to process are
blocked with ”IED blocked” and “IED test and blocked” modes. If physical outputs
General function block features
1MRS759142 F
1912 REX640
Technical Manual