EasyManua.ls Logo

ABB RELION REX640 - 4.2.4.7 Application

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 290: Combined forward directional overconductance and forward directional
oversusceptance characteristic. Left figure: the Conductance tilt Ang and
Susceptance tilt Ang settings equal zero degrees. Right figure: the setting
Conductance tilt Ang > 0 degrees and the setting Susceptance tilt Ang < 0 degrees.
Figure 291: Combined non-directional overconductance and non-directional
oversusceptance characteristic
The non-directional overconductance and non-directional
oversusceptance characteristic provides a good sensitivity and
selectivity when the characteristic is set to cover the total admittance
of the protected feeder with a proper margin.
The sign of the admittance characteristic settings should be considered
based on the location of characteristic boundary in the admittance plane.
All forward-settings are given with positive sign and reverse-settings
with negative sign.
Protection functions 1MRS759142 F
508 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals