Parameter Values (Range) Unit Step Default Description
7=Bus7
8=Bus8
Tie 7 busbar B Num
0=Not configured
1=Bus1
2=Bus2
3=Bus3
4=Bus4
5=Bus5
6=Bus6
7=Bus7
8=Bus8
0=Not configured Busbar B number
of tie breaker 7
Tie 8 busbar A Num
0=Not configured
1=Bus1
2=Bus2
3=Bus3
4=Bus4
5=Bus5
6=Bus6
7=Bus7
8=Bus8
0=Not configured Busbar A number
of tie breaker 8
Tie 8 busbar B Num
0=Not configured
1=Bus1
2=Bus2
3=Bus3
4=Bus4
5=Bus5
6=Bus6
7=Bus7
8=Bus8
0=Not configured Busbar B number
of tie breaker 8
Wait time signal
status
0...100 ms 1 50 Wait time between
Load/Unload signal
and GCB status
Wait time status
signal
0...100 ms 1 50 Wait time between
GCB status and
Load/Unload signal
7.5.9 DGMGAPC Monitored data
Table 1355: DGMGAPC Monitored data
Name
Type Values (Range) Unit Description
I_MAX FLOAT32 0.00...5.00 xIn Maximum of the three
phase input currents
F_CALC_LIMIT FLOAT32 0.00...2.00 xFn Calculated Freq limit in
governor compensated
droop mode
GEN_DATA INT32 0...8191 Generator data sent on
GOOSE for usage in
Ntw DGMGAPC
P_LOCAL FLOAT32 -499999.9...499999.9 kW Active power output of
generator
Table continues on the next page
Condition monitoring functions 1MRS759142 F
1430 REX640