5.3.6 Signals
5.3.6.1 TRPPTRC Input signals
Table 1124: TRPPTRC Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block of function
OPERATE BOOLEAN 0=False Operate
RST_LKOUT BOOLEAN 0=False Input for resetting
the circuit breaker
lockout function
5.3.6.2 TRPPTRC Output signals
Table 1125: TRPPTRC Output signals
Name Type Description
TRIP BOOLEAN General trip output signal
CL_LKOUT BOOLEAN Circuit breaker lockout out-
put (set until reset)
5.3.7 TRPPTRC Settings
Table 1126: TRPPTRC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Trip pulse time 20...60000 ms 1 250 Minimum duration
of trip output sig-
nal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched Select the opera-
tion mode for trip
output
5.3.8 TRPPTRC Monitored data
Table 1127: TRPPTRC Monitored data
Name Type Values (Range) Unit Description
TRPPTRC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection related functions 1MRS759142 F