ABB RELION REX640 - 5.3.6.1 TRPPTRC Input signals; 5.3.6.2 TRPPTRC Output signals; 5.3.7 TRPPTRC Settings; 5.3.8 TRPPTRC Monitored data

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3.6 Signals
5.3.6.1 TRPPTRC Input signals
Table 1124: TRPPTRC Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block of function
OPERATE BOOLEAN 0=False Operate
RST_LKOUT BOOLEAN 0=False Input for resetting
the circuit breaker
lockout function
5.3.6.2 TRPPTRC Output signals
Table 1125: TRPPTRC Output signals
Name Type Description
TRIP BOOLEAN General trip output signal
CL_LKOUT BOOLEAN Circuit breaker lockout out-
put (set until reset)
5.3.7 TRPPTRC Settings
Table 1126: TRPPTRC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Trip pulse time 20...60000 ms 1 250 Minimum duration
of trip output sig-
nal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched Select the opera-
tion mode for trip
output
5.3.8 TRPPTRC Monitored data
Table 1127: TRPPTRC Monitored data
Name Type Values (Range) Unit Description
TRPPTRC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection related functions 1MRS759142 F
1178 REX640
Technical Manual