Parameter Values (Range) Unit Step Default Description
2=DFT
3=Peak-to-Peak
Min operate current 0.5...100.0 %In 0.1 0.5 Minimum operating
current
Min operate volt-
age
1.0...100.0 %Un 0.1 1.0 Minimum operating
voltage
Correction angle 0.0...10.0 deg 0.1 0.0 Characteristic cor-
rection angle in
IoCos and IoSin
mode
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt. Reference quantity
used to determine
fault direction
DEFHPDEF Settings
Table 547: DEFHPDEF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.10...40.00 xIn 0.01 0.10 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
15=IEC Def. Time Selection of time
delay curve type
Operate delay time 40...300000 ms 10 40 Operate delay time
Characteristic an-
gle
-179...180 deg 1 -90 Characteristic an-
gle
Max forward angle 0...180 deg 1 80 Maximum phase
angle in forward di-
rection
Max reverse angle 0...180 deg 1 80 Maximum phase
angle in reverse di-
rection
Min forward angle 0...180 deg 1 80 Minimum phase an-
gle in forward di-
rection
Min reverse angle 0...180 deg 1 80 Minimum phase an-
gle in reverse direc-
tion
Voltage start value 0.010...1.000 xUn 0.001 0.010 Voltage start value
Table 548: DEFHPDEF Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
1=Immediate Selection of reset
curve type
Table continues on the next page
Protection functions 1MRS759142 F
478 REX640
Technical Manual