9.6.10 Technical data
Table 1526: ASGCSYN Technical data
Characteristic Value
Measurement accuracy
At the frequency f = f
n
Voltage difference: ±1.0 % or ±0.004 × U
n
Frequency difference: ±10 mHz
Phase angle difference: ±1° (±2.5° when f = f
n
±2 Hz)
Operation accuracy
MATCH_OK for voltage: ±0.001 × U
n
MATCH_OK for frequency: ±10 mHz
Operation time accuracy
Raise/Lower output pulse width:
±1.0 % of the set value or ±20 ms
Energizing time
for dead-bus closing:
±1.0 % of the set value or ±35 ms
Minimum Syn time
for SYNC_OK:
±1.0 % of the set value or ±60 ms
Reset time Typically 20 ms
Closing angle accuracy ±1°
9.7 Autosynchronizer for network breaker ASNSCSYN
(ANSI 25AUTOSYNCBT/T)
9.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autosynchronizer for network
breaker
ASNSCSYN AUTOSYNCBT/T 25AUTO-
SYNCBT/T
Control functions 1MRS759142 F
1586 REX640
Technical Manual