EasyManua.ls Logo

ABB RELION REX640 - 3.19.13 Real to integer 8-bit conversion T_R_TO_I8; 3.19.13.1 Function block; 3.19.13.2 Functionality; 3.19.13.3 Signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.19.13 Real to integer 8-bit conversion T_R_TO_I8
3.19.13.1 Function block
Figure 114: Function block
3.19.13.2 Functionality
The real to integer 8-bit conversion function T_R_TO_I8 converts a real to an integer
8-bit value. The real value is floored to integer value. The output quality follows the
input quality information.
If the real value is 10.6, 10.5, 10.4, –10.6, –10.5, –10.4, the integer value is
converted to 10, 10, 10, –11, –11, –11, respectively.
3.19.13.3 Signals
Table 182: T_R_TO_I8 Input signals
Name Type Default Description
REAL_IN FLOAT32 0 Real input value
Table 183: T_R_TO_I8 Output signals
Name Type Description
INT8_OUT INT8 Integer output value
1MRS759142 F Basic functions
REX640
Technical Manual
225