3.25.1.4 Settings
Table 347: RCHLCCH Settings
Parameter Values (Range) Unit Step Default Description
Redundant mode
Off
PRP
HSR
Mode selection for Ethernet
switch on redundant commu-
nication modules. The "None"
mode is used with normal and
Self-healing Ethernet topologies.
Filter Mode A_B
Off
SMV
GOOSE
GOOSE & SMV
Off
Filtering selection for message
types
Goose rate limiter
A_B
0.512...90.000 10.000 Goose rate limit (Mbps)
SMV rate limit A_B 0.512...90.000 70.000 Sampled measured values rate
limit (Mbps)
Def. rate limit A_B 0.512...90.000 8.000 Default rate limit (Mbps)
3.25.1.5 Monitored data
Monitored data is available in four locations.
Monitoring> Communication> Ethernet> Activity> CHLIV_A
Monitoring> Communication/> Ethernet> Activity> REDCHLIV_B
Monitoring> Communication> Ethernet> Link statuses> LNKLIV_A
Monitoring> Communication> Ethernet> Link statuses> REDLNKLIV_B
3.25.1.6 Diagnostics
Diagnostics data is available in Monitoring> Communication> Ethernet>
Diagnostics> A_B.
Table 348: Diagnostic parameters for the redundant Ethernet channels LAN A and LAN B
Parameter Values (Range) Unit Step Default Description
Reset counters FALSE / TRUE FALSE Reset counters command
GOOSE limit count 0...1000000 0 Goose rate limit exceed count
SMV limit count 0...1000000 0 Sampled measured values limit
exceed count
Ucast limit count 0...1000000 0 Unicast rate limit exceed count
Def. limit count 0...1000000 0 Default rate limit exceed count
GOOSE limit alarm FALSE / TRUE FALSE Goose rate limit exceed alarm
SMV limit alarm FALSE / TRUE FALSE Sampled measured values limit
alarm
Ucast limit alarm FALSE / TRUE FALSE Unicast rate limit exceed alarm
Def. limit alarm FALSE / TRUE FALSE Default rate limit exceed alarm
3.25.2 Ethernet channel supervision SCHLCCH