Parameter Values
(Range)
Unit Step Default Description
Counter Red
rate
2.0...250.0 s/h 0.1 60.0 Start time
counter re-
duction rate
Cumulative
time Lim
1...500 s 1 10 Cumulative
time based
restart inhibit
limit
Emg start Red
rate
0.00...100.00 % 0.01 20.00 Start time re-
duction fac-
tor when
emergency
start is On
Restart inhib-
it time
0...250 min 1 30 Time delay
between con-
secutive
startups
Ini start up
counter
0...999999 1 0 Initial value
for the
START_CNT
Table 1041: STTPMSU Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Motor standstill A 0.01...0.20 xIn 0.01 0.12 Current limit to
check for motor
standstill condition
4.10.9 STTPMSU Monitored data
Table 1042: STTPMSU Monitored data
Name
Type Values (Range) Unit Description
START_CNT INT32 0...999999 Number of motor start-
ups occurred
START_TIME FLOAT32 0.0...999.9 s Measured motor latest
startup time in sec
T_ST_CNT FLOAT32 0.0...99999.9 s Cumulated start-up
time in sec
T_RST_ENA INT32 0...999 min Time left for restart
when lockstart is ena-
bled in minutes
IIT_RL FLOAT32 0.00...100.00 % Thermal stress relative
to set maximum ther-
mal stress
STALL_RL FLOAT32 0.00...100.00 % Start time relative to
the operate time for
stall condition
STTPMSU Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions 1MRS759142 F
1104 REX640
Technical Manual