ABB RELION REX640 - 4.4 Unbalance protection; 4.4.1 Negative-sequence overcurrent protection NSPTOC (ANSI 46 M); 4.4.1.1 Identification; 4.4.1.2 Function block

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3.8.12 Technical data
Table 733: MHZPDIF Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured current:
f
n
±2 Hz
±1.5% of the set value or 0.002 × I
n
Start time
1, 2
I
Fault
= 2.0 × set
Start Value
(one
phase fault)
Minimum Typical Maximum
13 ms 17 ms 21 ms
I
Fault
= 2.0 ×
set
Start Value
(three phases
fault)
11 ms 14 ms 17 ms
Reset time <40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite
time mode
±1.0% of the set value of ±20 ms
4.4 Unbalance protection
4.4.1 Negative-sequence overcurrent protection NSPTOC (ANSI
46M)
4.4.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overcurrent pro-
tection
NSPTOC I2>M 46M
1
Measurement mode
= “Peak-to-Peak”, current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2
Includes the delay of the signal output contact
1MRS759142 F Protection functions
REX640
Technical Manual
819