Table 77: Station authority level “L,S,S+R,L+S,L+S+R” using R/L button
L/R Control L/R Control status Control access
R/L button CTRL.LLN0.LocS
ta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user IEC 61850 client
2
IEC 61850
client
3
Local FALSE FALSE 1 x
Remote FALSE TRUE 7 x x
Remote TRUE FALSE 3 x
Local + Remote FALSE TRUE 6 x x x
Local + Remote TRUE TRUE 5 x x
Off FALSE FALSE 0
Table 78: Station authority level “L,S,S+R,L+S,L+S+R” using CONTROL function block
L/R Control L/R Control status Control access
R/L button CTRL.LLN0.LocS
ta
4
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user IEC 61850 client
5
IEC 61850
client
6
CTRL_OFF FALSE FALSE 0
CTRL_LOC FALSE FALSE 1 x
CTRL_STA FALSE FALSE 3 x
CTRL_REM
7
TRUE TRUE 3 x
CTRL_REM FALSE TRUE 7 x x
CTRL_ALL FALSE TRUE 6 x x x
CTRL_ALL
7
TRUE TRUE 5 x x
3.8.8 Control mode
The function has two outputs BEH_TST and BEH_BLK which are activated in test
mode according to
Table 79
.
Table 79: Control mode
Control mode Description Control BEH_BLK
On Normal operation FALSE
Blocked Control function commands blocked TRUE
Off Control functions disabled FALSE
For more information, see the Test mode chapter in this manual.
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
4
Station client reserves the control operating by writing controllable point LocSta.
5
Client IEC 61850 command originator category is remote.
6
Client IEC 61850 command originator category is station.
7
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
1MRS759142 F Basic functions
REX640
Technical Manual