Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
change the hardware mod-
ule in slot D.
Internal Fault
Conf. error, Slot
F
-35 Start up error: Card
in slot F is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No No Yes Check that the card in slot
F is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot F.
Internal Fault
Conf. error, Slot
G
-36 Start up error: Card
in slot G is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No No Yes Check that the card in slot
G is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot G.
Internal Fault
Conf. error, Slot
A1
-37 Start up error: Card
in slot A1 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No No Yes Check that the card in slot
A1 is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot A1.
Internal Fault
Card error, Slot
C
-40 Card in slot C is
faulty.
Yes No Yes Exchange the hardware
module in slot C.
Internal Fault
Card error, Slot
E
-41 Card in slot E is
faulty.
Yes No Yes Exchange the hardware
module in slot E.
Internal Fault
Card error, Slot
A2
-42 Card in slot A2 is
faulty.
Yes No Yes Exchange the communica-
tion module in slot A2.
Internal Fault
Card error, Slot
B
-43 Card in slot B is
faulty.
Yes No Yes Exchange the hardware
module in slot B.
Internal Fault
Card error, Slot
D
-44 Card in slot D is
faulty.
Yes No Yes Exchange the hardware
module in slot D.
Internal Fault
Card error, Slot
F
-45 Card in slot F is
faulty.
Yes No Yes Exchange the hardware
module in slot F.
Internal Fault
Card error, Slot
G
-46 Card in slot G is
faulty.
Yes No Yes Exchange the hardware
module in slot G.
Internal Fault
Card error, Slot
A1
-47 Card in slot A1 is
faulty.
Yes No Yes Exchange the hardware
module in slot A1.
Internal Fault
640-Prod. Li-
cense error
-62 Runtime error:
Product license er-
ror, license file is
not found or is
wrong
No No Yes If SW update under Modifi-
cation Sales has been car-
ried out, redo the update. If
not recovered, contact your
nearest ABB representative
to check the next possible
corrective action.
Basic functions 1MRS759142 F
106 REX640