Figure 35: Redundant protection fail-safe principle, example 1
J01 Incomer feeder panel
J0x Load feeder panels
Q0 Circuit breaker (CB)
TO Relay trip output
SO Relay start output
A1 Protection relay
R1 Auxiliary relay
TC CB trip coil
F1 Miniature circuit breaker
In example 1, the fail-safe approach aims at securing circuit breaker tripping even
if a relay fails. The incomer panel relay indicates the start of selected protection
functions. This start signal is distributed to all load feeder panels. If a relay in the
load feeder panel indicates an IRF status, the start signal of the incomer panel
relay results in circuit breaker tripping. This approach offers basic protection for a
load feeder while the actual protection relay performs a self-supervision controlled
restart sequence.
TC1
TC2
Control +
Control -
-A1
-A1
-TO1
-F1
+J02-F1 control -
+J02-F1 control +
-Q0
-TO2
+J02 -A1
TC1
TC2
Control +
Control -
-A1
-A1
-TO1
-F1
+J01-F1 control -
+J01-F1 control +
-Q0
-TO2
+J01 -A1
AUX. POWER
AUX. POWER
+J01 +J02
Figure 36: Redundant protection fail-safe principle, example 2
Basic functions
1MRS759142 F
114 REX640
Technical Manual