Permissive underreaching transfer trip scheme PUTT
The permissive underreach scheme is enabled with
Scheme type
= "Permissive
Underreach".
In the permissive underreach scheme, the start signal from the underreaching
(instantaneous) residual overcurrent function DEFHPDEF is connected to the CSUR
input to create a CS_PRM signal. The duration of the CSUR input signal can be
prolonged by the
Carrier Min Dur
setting to ensure a sufficient duration of the
CS_PRM signal.
In the permissive underreach scheme, the CR_PRM signal or CRL signal, if
the unblocking function is enabled, is used to allow the overreaching residual
overcurrent function DEFLPDEF to trip (activation of the OPERATE output) after the
pick-up delay
Coordination time
. The start signal from the overreaching function is
connected to the CACC input. A general start signal in the forward direction can also
be connected to the CACC input.
The CS_PRM signal is also generated if the CR_PRM signal is received and the local
carrier acceleration signal CACC is active.
Activating the BLOCK input totally blocks the permissive underreach scheme. The
CS_PRM and OPERATE outputs can be blocked by the BLK_CS_OPR input.
~
~
CB_A
CB_B
Z2_START
TRIP_CB_A
TRIP_CB_B
DEFH_START
DEFL_START
Bus A
Bus B
3
3
Figure 712: Simplified functional diagram of the permissive underreach scheme
Permissive overrreaching transfer trip scheme POTT
The permissive overreach scheme is enabled with
Scheme type
= "Permissive
Overreach".
In this scheme, the START signal from the overreaching residual overcurrent
function DEFLPDEF is connected to the CSOR input to create a CS_PRM signal.
The CS_PRM signal can also be issued simultaneously from the underreaching
residual overcurrent function DEFHPDEF. In this case, the start signal from the
Protection related functions 1MRS759142 F
1254 REX640
Technical Manual

Table of Contents