Time settings
Table 57: Non group settings
Parameter Values (Range) Unit Step Default Description
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-103
1=SNTP Time synchroniza-
tion source
PTP Profile
1=IEEE
C37.238-2011
2=IEC 61850-9-3
1=IEEE
C37.238-2011
Profile Selection for
the Precision Time
Protocol
PTP domain ID 0...255 1 0 The domain is iden-
tified by an inte-
ger, the domain-
Number, in the
range of 0 to 255.
PTP priority 1 0...255 1 128 PTP priority 1, in
the range of 0 to
255.
PTP priority 2 0...255 1 128 PTP priority 2, in
the range of 0 to
255.
PTP Slave-only
0=False
1=True
0=False If true, the IED can-
not become a clock
master
Time master mode
1=Master with fi-
nite holdover
2=Master with in-
finite holdover
1=Master with fi-
nite holdover
Device Time Master
Mode
Clear clock list
0=False
1=True
0=False Clears the stored
master clock list
Time Syn Src Tmm 1...65535 min 1 3 Time synchroniza-
tion timeout for
legacy protocols as
clock source (Mod-
bus, IEC103, IEC101,
IEC104 and DNP)
Table 58: Non group settings
Parameter
Values (Range) Unit Step Default Description
Date 0 Date
Time 0 Time
Local time offset -840...840 min 1 0 Local time offset in
minutes
Table 59: Non group settings
Parameter
Values (Range) Unit Step Default Description
IP SNTP primary 192.168.2.166 IP address for SNTP
primary server
IP SNTP secondary 192.168.2.165 IP address for SNTP
secondary server
Basic functions 1MRS759142 F
128 REX640
Technical Manual