IEC 61850
remote
IED
IEC 61850
remote
REMOTE LOCAL OFF
IEC 61850
remote
IED
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
Figure 51: Station authority is “L,R”
When station authority level “L,R” is used, control access can be selected using R/L
button or CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta and
CONTROL function block inputs CTRL_STA and CTRL_ALL are not applicable for this
station authority level.
Table 71: Station authority level “L,R” using R/L button
L/R control L/R control status Control access
R/L button CTRL.LLN0.LocSta CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKey
HMI
Local user IEC 61850 client
1
Local N/A FALSE 1 x
Remote N/A FALSE 2 x
Off N/A FALSE 0
Table 72: Station authority “L,R” using CONTROL function block
L/R control L/R control status Control access
Control FB input CTRL.LLN0.LocSta CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKey
HMI
Local user IEC 61850 client
2
CTRL_OFF N/A FALSE 0
CTRL_LOC N/A FALSE 1 x
CTRL_STA N/A FALSE 0
CTRL_REM N/A FALSE 2 x
CTRL_ALL N/A FALSE 0
1
Client IEC 61850 command originator category check is not performed.
2
Client IEC 61850 command originator category check is not performed.
1MRS759142 F Basic functions
REX640
Technical Manual
137