Parameter Values (Range) Unit Step Default Description
Alarm Op number 0...99999 1 200 Alarm limit for
number of opera-
tions
Lockout Op num-
ber
0...99999 1 300 Lock out limit for
number of opera-
tions
Current exponent 0.00...5.00 0.01 2.00 Current exponent
setting for energy
calculation
Difference Cor time -10...10 ms 1 5 Corr. factor for
time dif in aux. and
main contacts open
time
Alm Acc currents
Pwr
0.00...20000.00 0.01 2500.00 Setting of alarm
level for accumula-
ted currents power
LO Acc currents
Pwr
0.00...20000.00 0.01 2500.00 Lockout limit set-
ting for accumula-
ted currents power
Initial CB Rmn life 0...99999 1 5000 Initial value for the
CB remaining life
Rated Op current 100.00...6300.00 A 0.01 1000.00 Rated operating
current of the
breaker
Rated fault current 500.00...99999.00 A 0.01 5000.00 Rated fault current
of the breaker
Op number rated 1...99999 1 10000 Number of opera-
tions possible at
rated current
Op number fault 1...10000 1 1000 Number of opera-
tions possible at
rated fault current
Inactive Alm days 0...9999 1 2000 Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calcu-
lation mode selec-
tion
Table 1313: SSCBR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Opening time Cor -100...100 ms 1 10 Correction factor
for open travel time
in ms
Closing time Cor -100...100 ms 1 10 Correction factor
for CB close travel
time in ms
Counter initial Val 0...99999 1 0 The operation num-
bers counter initial-
ization value
Ini Acc currents Pwr 0.00...20000.00 0.01 0.00 Initial value for ac-
cumulation energy
(Iyt)
Life alarm level 0...99999 1 500 Alarm level for CB
remaining life
Pressure alarm
time
0...60000 ms 1 10 Time delay for gas
pressure alarm in
ms
Pres lockout time 0...60000 ms 10 10 Time delay for gas
pressure lockout in
ms
Ini inactive days 0...9999 1 0 Initial value of the
inactive days coun-
ter
Inactive Alm hours 0...23 h 1 0 Alarm time of the
inactive days coun-
ter in hours
Condition monitoring functions 1MRS759142 F
1374 REX640
Technical Manual