Function Settings for limit value supervision
Low limit
High-high limit
A Hi high limit res
Low-low limit
Frequency measurement (FMMXU) High limit
F high limit
Low limit
F low limit
High-high limit
F high high limit
Low-low limit
F low low limit
Residual voltage measurement (RESVMMXU) High limit
V high limit res
Low limit
High-high limit
V Hi high limit res
Low-low limit
Phase sequence current measurement
(CSMSQI)
High limit
Ps Seq A high limit
,
Ng Seq A high limit
,
Zro A high limit
Low limit
Ps Seq A low limit
,
Ng
Seq A low limit
,
Zro A
low limit
High-high limit
Ps Seq A Hi high Lim
,
Ng Seq A Hi high Lim
,
Zro A Hi high Lim
Low-low limit
Ps Seq A low low Lim
,
Ng Seq A low low Lim
,
Zro A low low Lim
Phase sequence voltage measurement
(VSMSQI)
High limit
Ps Seq V high limit
,
Ng Seq V high limit
,
Zro V high limit
Low limit
Ps Seq V low limit
,
Ng
Seq V low limit
,
Zro V
low limit
High-high limit
Ps Seq V Hi high Lim
,
Ng Seq V Hi high Lim
,
Zro V Hi high Lim
Low-low limit
Ps Seq V low low Lim
,
Ng Seq V low low Lim
,
Three-phase power and energy measurement
(PEMMXU)
High limit
Low limit
High-high limit
Low-low limit
Deadband supervision
The deadband supervision function reports the measured value according to
integrated changes over a time period. In
Figure 804
the values are reported at
points Y1, Y2, Y3 and Y4. There is no value report at the end of |A3 + A4 + A5 + A6
+ A7| because the positive and negative areas counteract each other. The integrated
changes, |A3 + A4 + A5 + A6 + A7|, equal approximately zero.
1MRS759142 F
Measurement functions
REX640
Technical Manual
1437