EasyManua.ls Logo

ABB RELION REX640 - Page 1532

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
ESPOSOPEN BOOLEAN 0=False Signal for open po-
sition of earthing
switch
ESPOSCLOSE BOOLEAN 0=False Signal for close po-
sition of earthing
switch
REED BOOLEAN 0=False Signal for close posi-
tion of reed contact
ENA_DCOPEN BOOLEAN 1=True Enables opening
command for discon-
nector
ENA_DCCLOSE BOOLEAN 1=True Enables closing com-
mand for disconnec-
tor
ENA_ESOPEN BOOLEAN 1=True Enables opening
command for earth-
ing switch
ENA_ESCLOSE BOOLEAN 1=True Enables closing com-
mand for earthing
switch
BLK_DCOPEN BOOLEAN 0=False Blocks opening of
disconnector
BLK_DCCLOSE BOOLEAN 0=False Blocks closing of dis-
connector
BLK_ESOPEN BOOLEAN 0=False Blocks opening of
earthing switch
BLK_ESCLOSE BOOLEAN 0=False Blocks closing of
earthing switch
AU_DCOPEN BOOLEAN 0=False Auxiliary open discon-
nector
AU_DCCLOSE BOOLEAN 0=False Auxiliary close dis-
connector
AU_ESOPEN BOOLEAN 0=False Auxiliary open earth-
ing switch
AU_ESCLOSE BOOLEAN 0=False Auxiliary close earth-
ing switch
ITL_BYPASS BOOLEAN 0=False Discards enable inter-
locking when TRUE
NO_FAULT BOOLEAN 1=True RIO600 SCM no fault
DEVICE_ERR BOOLEAN 0=False RIO600 SCM device
error
RELEASE BOOLEAN 0=False RIO600 SCM release
information
NO_ACT BOOLEAN 1=True RIO600 SCM no mo-
tor action
Table continues on the next page
Control functions 1MRS759142 F
1532 REX640
Technical Manual

Table of Contents