Table 1544: Settings of ASCGAPC of NSCB4 for given example
Settings Suggested values Description
ASC CB Num1 Non source CB 4 ASC1 host circuit breaker number 4
Number of sources 3 Total number of sources present in the sys-
tem
Number of NonSrc CB 4 Number of bus coupler or grid transformer
CB in the system
Src1 bus A Num Bus 3 Source1 CB connected bus A number
Src2 bus A Num Bus 2 Source1 CB connected bus A number
Src3 bus A Num Bus 4 Source1 CB connected bus A number
NonSrc1 bus A1 Num Bus 1 Non-source CB1 connected bus A1 number
NonSrc1 bus A2 Num Grid Non-source CB1 connected bus A2 number
NonSrc2 bus A1 Num Bus 1 Non-source CB2 connected bus A1 number
NonSrc2 bus A2 Num Bus 2 Non-source CB2 connected bus A2 number
NonSrc3 bus A1 Num Bus 2 Non-source CB3 connected bus A1 number
NonSrc3 bus A2 Num Bus 3 Non-source CB3 connected bus A2 number
NonSrc4 bus A1 Num Bus 3 Non-source CB4 connected bus A1 number
NonSrc4 bus A2 Num Bus 4 Non-source CB4 connected bus A2 number
Table 1545: Settings of ASCGAPC of SCB1 for given example
Settings Suggested values Description
ASC CB Num1 Source CB 1 ASC1 host circuit breaker number 1
Number of sources 3 Total number of sources present in system
Number of NonSrc CB 4 Number of bus coupler or grid transformer
CB in the system
Table 1546: Settings of ASCGAPC of SCB2 for given example
Settings Suggested values Description
ASC CB Num1 Source CB 2 ASC1 host circuit breaker number 2
Number of sources 3 Total number of sources present in system
Number of NonSrc CB 4 Number of bus coupler or grid transformer
CB in the system
Table 1547: Settings of ASCGAPC of SCB3 for given example
Settings Suggested values Description
ASC CB Num1 Source CB 3 ASC1 host circuit breaker number 3
Number of sources 3 Total number of sources present in system
Number of NonSrc CB 4 Number of bus coupler or grid transformer
CB in the system
The subnetwork numbers of eight power sources are available in monitored data
SBNW_SRC1...SBNW_SRC8. The subnetwork numbers of NSCBs are available in
1MRS759142 F
Control functions
REX640
Technical Manual
1613