Parameter Values (Range) Unit Step Default Description
3=Parallel manual
4=Auto parallel
5=Input control
6=Command
Custom Man block-
ing
1=Custom disabled
2=OC
3=UV
4=OC, UV
5=EXT
6=OC, EXT
7=UV, EXT
8=OC, UV, EXT
2=OC Customized man-
ual blocking
Parallel trafos 0...10 1 0 Number of paral-
lel transformers in
addition to own
transformer
Delay characteristic
0=Inverse time
1=Definite time
1=Definite time Selection of delay
characteristic
Band width voltage 1.00...18.00 %Un 0.01 3.00 Allowed deviation
of the control volt-
age
Load current limit 0.10...5.00 xIn 0.01 2.00 Load current block-
ing limit
Block lower voltage 0.10...1.20 xUn 0.01 0.70 Voltage limit, where
further voltage low-
ering commands
are blocked
Runback raise V 0.80...2.40 xUn 0.01 1.25 Voltage limit, where
fast lower com-
mands takes place
Cir current limit 0.10...5.00 xIn 0.01 0.15 Blocking limit for
high circulating
current
LTC pulse time 500...10000 ms 100 1500 Output pulse dura-
tion, common for
raise and lower pul-
ses
Regulation mode
1=Forward
2=Bi-dir(meas)
3=Bi-dir(calc)
4=Auto select
1=Forward Regulation mode
Table 1585: OL5ATCC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Max operations in
1h
0...10000 1 100 Allowed number of
controls per one
hour sliding win-
dow
Cmd error delay
time
10...50 s 1 20 Time delay before
command error will
be activated
Follower delay time 6...20 s 1 6 Time delay be-
tween successive
follower commands
by a master
Alarms enabled
0=False
1=True
1=True Alarm selection
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1725