Name Type Values (Range) Unit Description
MOT_RUN_TIME INT32 0...999999 h Total arc suppression
coil motor run time
(hours)
CALIB_RSL Enum
1=Calibration success-
ful
2=Calibration ongoing
3=Calibration failed
4=Not calibrated
Calibration result
CALIB_STS Enum
1=Detect end switches
2=Move to middle posi-
tion
3=Detect mechanical
play
4=Detect after running
5=Detect potentiome-
ter gaps
6=Calibration not ongo-
ing
Calibration status
ALARM_STS Enum
1=No alarm
2=No movement detec-
ted
3=Movement into
wrong direction
4=Simultaneously indi-
cation from both end-
switches
5=Potentiometer maxi-
mum gap length excee-
ded
6=Potentiometer new
gap appeared
7=Maximum number of
potentiometer gaps ex-
ceeded
8=Check measurements
9=Umin not reached
10=Cannot obtain mini-
mum Uo variation
Alarm status
TUNING_STS Enum
1=Tuned successfully
2=Not tuned
3=Tuned at Umax
4=Tuned at low limit
(low end switch or low
operating limit)
5=Tuned at high limit
(high end switch or
high operating limit)
6=Tuning delay ongoing
7=Move to Ures min
8=Direction determina-
tion
9=Pick up 1st point
10=Pick up 2nd point
11=Pick up 3rd point
12=Calculate parame-
ters
Tuning status
Table continues on the next page
1MRS759142 F Control functions
REX640
Technical Manual
1755