EasyManua.ls Logo

ABB RELION REX640 - Page 1779

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Residual voltage transfer
The residual voltage transfer is utilized when a connection in the 1
st
phase
coincidence is not possible. Following conditions must be met for residual voltage
transfer:
transfer is running
both breakers are open
DISA_RES is FALSE
setting
Ena Res V transfer
allows transfer
if transfer is initiated manually, then ENA_FASTONLY must be FALSE
The connection of the stand-by feeder takes place when the voltage of the busbar
has subsided to a preset, permissible value. The threshold value for the busbar
voltage for residual voltage transfer is set with setting
Residual voltage limit
.
Residual voltage transfer is enabled with setting
Ena Res V transfer
.
The connection takes place without assessment of the angle or of the difference
frequency, thus in unsynchronized fashion. Because the voltage of the busbars has
however reached a sufficiently low residual voltage value, the transient effects of
the connection are manageable (momentary jolt, current needed for users to run up
again, voltage reduction).
Main feeder
breaker
Stand-by
feeder breaker
Main feeder
breaker open
command
Stand-by
feeder close
command
1
2
3
4
Figure 946: Signal diagram of residual voltage transfer
1
Busbar voltage
2 Voltage difference between stand-by and busbar voltage
3 Main feeder current
4 Stand-by feeder current
If DISA_RUN input is active, transfer is not allowed to complete until input is
deactivated.
1MRS759142 F
Control functions
REX640
Technical Manual
1779

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals