Name Type Default Description
DISA_2_1 BOOLEAN 0=False Disable transfer from
feeder 2 to feeder 1
DISA_FAST BOOLEAN 0=False Disable transfer
based on fast trans-
fer
DISA_FBBM BOOLEAN 0=False Disable transfer
based on fast break
before make
DISA_1ST_PH BOOLEAN 0=False Disable transfer
based on first phase
coincidence
DISA_RES BOOLEAN 0=False Disable transfer
based on residual
voltage
DISA_TDLY BOOLEAN 0=False Disable transfer
based on time delay
DISA_CBOPN BOOLEAN 0=False Disable transfer ini-
tiation based on CB
open transfer
DISA_DECOUPL BOOLEAN 0=False Disable decoupling
DISA_RUN BOOLEAN 0=False Disable transfer com-
pletion when active
ENA_FASTONLY BOOLEAN 0=False Enable fast transfer
only
POSOPN_CB1 BOOLEAN 0=False Signal for open po-
sition of apparatus
from I/O
POSCLS_CB1 BOOLEAN 0=False Signal for close po-
sition of apparatus
from I/O
POSOPN_CB2 BOOLEAN 0=False Signal for open po-
sition of apparatus
from I/O
POSCLS_CB2 BOOLEAN 0=False Signal for close po-
sition of apparatus
from I/O
RDYOPN_CB1 BOOLEAN 0=False Circuit breaker ready
to open feeder 1
RDYCLS_CB1 BOOLEAN 0=False Circuit breaker ready
to close feeder 1
RDYOPN_CB2 BOOLEAN 0=False Circuit breaker ready
to open feeder 2
RDYCLS_CB2 BOOLEAN 0=False Circuit breaker ready
to close feeder 2
RESET_REC BOOLEAN 0=False Reset recorded data
Table continues on the next page
Control functions 1MRS759142 F
1798 REX640
Technical Manual