Parameter Values (Range) Unit Step Default Description
3=Both
4=Off
Ena Time delay
transfer
1=1>2
2=2>1
3=Both
4=Off
3=Both Enable Time delay
transfer
Ena CB open trans-
fer
1=1>2
2=2>1
3=Both
4=Off
4=Off Enable transfer
based on CB open-
ing
Manual transfer
1=Off
2=On
3=Fast MBB
1=Off Enable manual
transfer
Max frequency Diff 0.05...2.50 Hz 0.01 1.00 Maximum frequen-
cy difference limit
for fast transfer
Maximum phase
lead
5...50 deg 1 20 Maximum phase
lead limit for fast
transfer
Maximum phase
lag
5...50 deg 1 20 Maximum phase
lag limit for fast
transfer
Max angle Diff
FBBM
5...90 deg 1 45 Max phase angle
allowed for fast
break before make
transfer
Maximum DfDt 5...40 1 40 Maximum DfDt lim-
it for transfer
Transfer delay time 100...200000 ms 1 2000 Time delayed trans-
fer activation time
Max Trn run time 100...200000 ms 1 5000 Maximum transfer
running time
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
3=From Cmd to
Curr
4=From Pos to Curr
1=From Cmd to Pos Travel time calcu-
lation mode selec-
tion
CB open alarm time 0...1000 ms 1 60 Alarm level setting
for open travel time
in ms
CB close alarm time 0...1000 ms 1 80 Alarm level setting
for close travel time
in ms
CB closing time Dif 0...1000 ms 1 10 Allowed closing
time difference for
alarm activation in
ms
Table 1613: HSABTC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Transfer wait time 100...200000 ms 10 5000 Transfer wait time
until new transfer is
allowed
Closing time of CB1 0...200 ms 1 60 Closing time of the
breaker feeder1
Closing time of CB2 0...200 ms 1 60 Closing time of the
breaker feeder2
Table continues on the next page
Control functions 1MRS759142 F
1802 REX640
Technical Manual