L1 L2 L3
current only)
ca
A B C
Figure 1021: AIM1001 module (two phase-to-phase VTs)
The two phase-to-phase VT connection is often referred as “open delta” (ANSI)
or as “V” (IEC) connection. The relay measures all three phase-to-phase voltages
using only two primary VTs. The relay will calculate the phase-to-ground voltages
internally, with the assumption that the three-phase system is balanced, i.e. residual
voltage is zero.
Protection relay's physical connections 1MRS759142 F
1924 REX640
Technical Manual