EasyManua.ls Logo

ABB RELION REX640 - Page 1941

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description PSM1001 PSM1002 PSM1003
80...120 % of U
n
(38.4...300 V DC)
Start-up threshold 16 V DC (24 V DC ×
67%)
77 V DC (110 V DC × 70
%)
Burden of auxiliary
voltage supply under
quiescent (P
q
)/ oper-
ating condition
DC <18.0 W (nomi-
nal)/ <25.0 W (max.)
DC <20.0 W (nomi-
nal)/ <25.0 W (max.)
AC <20.0 W (nomi-
nal)/ <25.0 W (max.)
DC <17.0 W (nominal)/
<25.0 W (max.)
Ripple in the DC auxil-
iary voltage
Max 15 % of the DC value (at frequency of 100 Hz)
Fuse type T8A/250 V T4A/250 V
Permissible frequency
band
50/60Hz +-10%
Table 1666: Power supply for the LHMI
Description Value
Nominal auxiliary voltage U
n
100, 110, 120, 220, 240 V AC, 50 and 60 Hz
24, 48, 60, 110, 125, 220, 250 V DC
Auxiliary voltage variation 38...110 % of U
n
(38...264 V AC)
80...120 % of U
n
(19.2...300 V DC)
Start-up threshold 19.2 V DC (24 V DC × 80 %)
Burden of auxiliary voltage supply under qui-
escent (P
q
)/operating condition
DC <6.0 W (nominal)/<14.0 W (max.)
AC <7.0 W (nominal)/<12.0 W (max.)
Ripple in the DC auxiliary voltage Max 15 % of the DC value (at frequency of 100
Hz)
Fuse type T3.15A/250V
Table 1667: Energizing inputs
Description Value
Rated frequency 50/60 Hz
Current inputs Rated current, I
n
0.2/1 A 1/5 A
2
Thermal withstand
capability:
Continuously
For 1 s
4 A
100 A
20 A
500 A
Dynamic current
withstand:
Half-wave value
250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Table continues on the next page
2
Residual current and/or phase current.
1MRS759142 F Technical data
REX640
Technical Manual
1941

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals