EasyManua.ls Logo

ABB RELION REX640 - Page 1950

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description Type test value Reference
Damped oscillatory magnetic
field immunity test
2 s
1 MHz
100 A/m
400 transients/s
IEC 61000-4-10
Voltage dips and short inter-
ruptions
0%/50 ms Criterion A
40%/200 ms Criterion C
70%/500 ms Criterion C
0%/5000 ms Criterion C
IEC 61000-4-11
IEC 61000-4-29
IEC 60255-26
Power frequency immunity
test
Common mode
Differential mode
Binary inputs only 300 V rms
150 V rms
IEC 61000-4-16
IEC 60255-26, class A
Emission tests
Conducted
0.15. 0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
1…3 GHz
3…6 GHz
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10 m distance
<47 dB (µV/m) quasi peak,
measured at 10 m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
Table 1688: Safety-related tests
Description Type test value Reference
Overvoltage category III IEC 60255-27
Pollution degree 2 IEC 60255-27
Insulation class Class I IEC 60255-27
Dielectric tests
500 V, 50 Hz, 1 min, RS-485
and IRIG-B
1 kV, 50 Hz, 1 min, across
open contacts
1.5 kV, 50 Hz, 1 min, Ethernet
RJ-45
IEC 60255-27
Table continues on the next page
Protection relay and functionality tests 1MRS759142 F