If ENA U MULT isTRUE
Effectivestart value Start value low
_ _ :
=
(Equation 29)
If ENA U MULT is FALSE
Effectivestart value Start value
_ _ :
=
(Equation 30)
Voltage and input control mode
If
Control mode
is set to "Voltage and input Ctrl", both the "Voltage control"
and "Input control" modes are used. However, the “Input control” functionality is
dominant over the “Voltage control” mode when ENA_LOW_LIM is active.
No voltage dependency mode
When
Control mode
is set to "No Volt dependency", the effective start value has no
voltage dependency and the function acts as a normal time overcurrent function
with effective start value being equal to the
Start value
setting.
Level detector
The measured phase currents are compared phasewise to the calculated effective
start value. If the measured value exceeds the calculated effective start value, the
Level detector reports the exceeding value to the phase selection logic. If the
ENA_MULT input is active, the effective start value is multiplied by the
Start value
Mult
setting.
Do not set the multiplier
Start value Mult
setting higher than necessary. If
the value is too high, the function may not operate at all during an inrush
followed by a fault, no matter how severe the fault is.
The start value multiplication is normally done when the inrush detection function
INRPHAR is connected to the ENA_MULT input.
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects
the phase or phases in which the measured current exceeds the setting. If the phase
information matches the
Num of start phases
setting, the phase selection logic
activates the Timer module.
Timer
Once activated, the Timer module activates the START output.
Depending on the value of the
Operating curve type
setting, the time characteristics
are according to DT or IDMT. When the operation timer has reached the value of
Operate delay time
in the DT mode or the maximum value defined by the inverse
time curve, the OPERATE output is activated.
When the user programmable IDMT curve is selected, the operation time
characteristics are defined by the settings
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.