Figure 342: Permissible time-touch voltage characteristics given in standard EN
50522
Time margin for practical circuit-breaker operate time can be applied with
setting
CB delay Comp
. Default time margin is 0 ms.
START and ST_EF outputs are activated when estimated effective earth-fault
current magnitude (considering the effect of settings
Reduction factor
and
Enable harmonics
) exceeds setting
EF current Str Val
and earth fault is detected,
and earth-fault current estimate is validated. Note that
Ena RF Compensation
=
“Enable” does not affect this start condition.
OPERATE and OP_EF outputs are activated according to the operate time - touch
voltage and earth potential rise requirements defined in standard EN 50522. i.e.
operate time is inversely proportional to the estimated fault current.
Reset timer is started if any of the above conditions for START is not anymore
valid. START and ST_EF outputs stay activated until the reset timer expires
(setting
Reset delay time
). After OPERATE output activation, START, ST_EF,
OPERATE and OP_EF outputs are reset immediately i.e. reset delay time is no
longer valid. During re-striking/intermittent earth faults, the very high current
transient may result to very fast operation times. In case longer operation time
during re-striking/intermittent earth faults is preferred and operation should
be based preferably on counted number of transients, then setting
Reset delay
time
should be set to low value, say 20-40 ms. Dedicated intermittent earth-fault
protection functionality based on counted number of transients is described in
Chapter 4.2.10.5.6 Intermittent earth-fault protection
.
Applicable settings are:
Reduction factor, EF current Str Val, CB delay Comp, UTp
multiplier, Maximum earthing Ris, IDMT stage Min Op Tm, IDMT stage Max Op
Tm, Reset delay time
.
It is important to note, that:
1MRS759142 F
Protection functions
REX640
Technical Manual
601