Figure 353: Permissible time-touch voltage characteristics given in standard
IEEE80 (metal-to-metal contact).
This operation mode can be also used when maximum allowed earthing voltage,
i.e. earth potential rise, vs. operation speed follows a relationship such as 750V/
t
[
sec
].
Time margin for practical circuit-breaker operate time can be applied with
setting
CB delay Comp
. Default setting is 0 ms.
START and ST_EF outputs are activated when estimated touch voltage
(considering the effect of settings
Reduction factor
and
Enable harmonics
)
exceeds setting
Touch Vol Str Val
and earth fault is detected and earth-fault
current estimate is validated. Note that
Ena RF Compensation
= “Enable” does
not affect this start condition.
OPERATE and OP_EF outputs are activated according to time-touch voltage
characteristics given in standard IEEE80 i.e. operate time is inversely
proportional to the estimated touch voltage.
Reset timer is started if any of the above conditions for START is not anymore
valid. START and ST_EF outputs stay activated until the reset timer expires
(setting
Reset delay time
). After OPERATE output activation, START, ST_EF,
OPERATE and OP_EF outputs are reset immediately i.e. reset delay time is no
longer valid.
During re-striking/intermittent earth faults, the very high current transient may
result to very fast operation times. In case longer operation during re-striking/
intermittent earth faults is preferred and operation should be based preferably
on counted number of transients, then setting
Reset delay time
should be
set to low value, say 20-40 ms. Dedicated intermittent earth-fault protection
functionality based on counted number of transients is described in
Chapter
4.2.10.5.6 Intermittent earth-fault protection
.
Applicable settings are:
Reduction factor, Maximum earthing Ris, Touch Vol Str
Val, CB delay Comp, IEEE multiplier, IDMT stage Min Op Tm, IDMT stage Max Op
Tm, Reset delay time
.
According to the standard IEEE80, the values of the permissible touch voltage U
Tp
as a function of the fault duration t
f
are defined as follows:
For body weight of 50 kg:
Protection functions
1MRS759142 F
620 REX640
Technical Manual