EasyManua.ls Logo

ABB RELION REX640 - Page 699

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 399: Example of two-winding power transformer differential
protection
The rated load of the transformer is calculated:
HV side: I
nT_Wnd1
= 25 MVA / (1.732 x 110 kV) = 131.2 A
LV side: I
nT_Wnd2
= 25 MVA / (1.732 x 21 kV) = 687.3 A
Settings:
CT ratio Cor Wnd 1
= 300 A / 131.2 A = “2.29”
CT ratio Cor Wnd 2
= 1000 A / 687.3 A = “1.45”
Vector group matching and elimination of the zero-sequence component
The vector group of the power transformer is numerically matched on the high
voltage and low voltage sides by means of the
Winding 1 type
,
Winding 2 type
and
Clock number
settings. Thus no interposing CTs are needed if there is only
a power transformer inside the protected zone. The matching is based on phase
shifting and a numerical delta connection in the protection relay. If the neutral of
a star-connected power transformer is earthed, any earth fault in the network is
perceived by the protection relay as a differential current. The elimination of the
zero-sequence component can be selected for that winding by setting the
Zro A
elimination
parameter.
Table 655: TR2PTDF settings corresponding to the power transformer vector
groups and zero-sequence elimination
Vector group of
the transformer
Winding 1 type Winding 2 type Clock number Zro A
Elimination
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
699

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals