EasyManua.ls Logo

ABB RELION REX640 - Page 703

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vector group of
the transformer
Winding 1 type Winding 2 type Clock number Zro A
Elimination
Zzn6 Z zn Clk Num 6 LV side
Zz8 Z z Clk Num 8 Not needed
ZNz8 ZN z Clk Num 8 Not needed
ZNzn8 ZN zn Clk Num 8 Not needed
Zzn8 Z zn Clk Num 8 Not needed
Zz10 Z z Clk Num 10 Not needed
ZNz10 ZN z Clk Num 10 Not needed
ZNzn10 ZN zn Clk Num 10 Not needed
Zzn10 Z zn Clk Num 10 Not needed
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
YNyn2 YN yn Clk Num 2 Not needed
Yyn2 Y yn Clk Num 2 Not needed
Yy4 Y y Clk Num 4 Not needed
YNy4 YN y Clk Num 4 Not needed
YNyn4 YN yn Clk Num 4 Not needed
Yyn4 Y yn Clk Num 4 Not needed
Yy6 Y y Clk Num 6 Not needed
YNy6 YN y Clk Num 6 HV side
YNyn6 YN yn Clk Num 6 HV & LV side
Yyn6 Y yn Clk Num 6 LV side
Yy8 Y y Clk Num 8 Not needed
YNy8 YN y Clk Num 8 Not needed
YNyn8 YN yn Clk Num 8 Not needed
Yyn8 Y yn Clk Num 8 Not needed
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
YNd1 YN d Clk Num 1 Not needed
Yd5 Y d Clk Num 5 Not needed
YNd5 YN d Clk Num 5 Not needed
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
703

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals