EasyManua.ls Logo

ABB RELION REX640 - Page 714

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
BLKD5H_C BOOLEAN
0=False
1=True
5th harmonic restraint
block phase C status
BLKDWAV_A BOOLEAN
0=False
1=True
Waveform blocking
phase A status
BLKDWAV_B BOOLEAN
0=False
1=True
Waveform blocking
phase B status
BLKDWAV_C BOOLEAN
0=False
1=True
Waveform blocking
phase C status
BLKD2HPHAR BOOLEAN
0=False
1=True
2nd harmonic restraint
blocking for PHAR LN,
combined
BLKD2HPHAR_A BOOLEAN
0=False
1=True
2nd harmonic restraint
blocking for PHAR LN,
phase A
BLKD2HPHAR_B BOOLEAN
0=False
1=True
2nd harmonic restraint
blocking for PHAR LN,
phase B
BLKD2HPHAR_C BOOLEAN
0=False
1=True
2nd harmonic restraint
blocking for PHAR LN,
phase C
BLKD5HPHAR BOOLEAN
0=False
1=True
5th harmonic restraint
blocking for PHAR LN,
combined
BLKD5HPHAR_A BOOLEAN
0=False
1=True
5th harmonic restraint
blocking for PHAR LN,
phase A
BLKD5HPHAR_B BOOLEAN
0=False
1=True
5th harmonic restraint
blocking for PHAR LN,
phase B
BLKD5HPHAR_C BOOLEAN
0=False
1=True
5th harmonic restraint
blocking for PHAR LN,
phase C
I_AMPL_A1 FLOAT32 0.00...40.00 xIr Connection group com-
pensated primary cur-
rent phase A
I_AMPL_B1 FLOAT32 0.00...40.00 xIr Connection group com-
pensated primary cur-
rent phase B
I_AMPL_C1 FLOAT32 0.00...40.00 xIr Connection group com-
pensated primary cur-
rent phase C
I_AMPL_A2 FLOAT32 0.00...40.00 xIr Connection group com-
pensated secondary
current phase A
I_AMPL_B2 FLOAT32 0.00...40.00 xIr Connection group com-
pensated secondary
current phase B
I_AMPL_C2 FLOAT32 0.00...40.00 xIr Connection group com-
pensated secondary
current phase C
ID_A FLOAT32 0.00...80.00 xIr Differential Current
phase A
ID_B FLOAT32 0.00...80.00 xIr Differential Current
phase B
ID_C FLOAT32 0.00...80.00 xIr Differential Current
phase C
IB_A FLOAT32 0.00...80.00 xIr Biasing current phase A
IB_B FLOAT32 0.00...80.00 xIr Biasing current phase B
IB_C FLOAT32 0.00...80.00 xIr Biasing current phase C
Table continues on the next page
Protection functions 1MRS759142 F
714 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals