Figure 406: Functional module diagram
Differential calculation
TR3PTDF operates phasewise on the difference of incoming and outgoing currents.
The positive direction of the currents is towards the protected object.
Winding 1
(usually HV)
Winding 2
(usually LV)
1W
I
Winding 3
(usually tertiary)
2W
I
3W
I
Figure 407: Single-line diagram of the positive direction of the currents in a
threewinding transformer
The normalized amplitude of the differential current per phase Id is obtained using
the equation:
Protection functions
1MRS759142 F
718 REX640
Technical Manual