EasyManua.ls Logo

ABB RELION REX640 - Page 989

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
R0 zone 2 0.00...3000.00 ohm 0.01 160.00 Zero sequence re-
sistive reach, zone
2
X0 zone 2 0.00...3000.00 ohm 0.01 160.00 Zero sequence re-
active reach, zone 2
Factor K0 zone 2 0.00...5.00 0.01 1.00 Residual compen-
sation factor mag-
nitude, zone 2
Factor K0 angle
Zn2
-179...180 deg 1 0 Residual compen-
sation factor angle,
zone 2
Min Ris Gnd Rch
Zn2
0.00...500.00 ohm 0.01 100.00 Minimum resistive
reach of PE-loops,
zone 2
Max Ris Gnd Rch
Zn2
0.00...500.00 ohm 0.01 100.00 Maximum resistive
reach of PE-loops,
zone 2
Gnd operate Dl Zn2 20...60000 ms 1 20 Time delay to op-
erate of PE-loops,
zone 2
Directional mode
Zn3
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode,
zone 3
Op Mod PP loops
Zn3
0=False
1=True
0=False Enable PP/3P-loop
measurement, zone
3
PP Op delay Mod
Zn3
0=False
1=True
1=True Enable operate tim-
er for PP/3P-loops,
zone 3
R1 zone 3 0.00...3000.00 ohm 0.01 40.00 Positive sequence
resistive reach,
zone 3
X1 zone 3 0.00...3000.00 ohm 0.01 40.00 Positive sequence
reactive reach, zone
3
X1 reverse zone 3 0.00...3000.00 ohm 0.01 40.00 Pos. seq. reactive
reach in rev. dir.,
non-dir. zone 3
Z1 zone 3 0.01...3000.00 ohm 0.01 56.57 Positive sequence
reach, zone 3
Z1 angle zone 3 15.0...90.0 deg 0.1 45.0 Positive sequence
line angle, zone 3
Z1 reverse zone 3 0.00...3000.00 ohm 0.01 56.57 Positive sequence
reach in rev. dir.,
non-dir. zone 3
Min Ris PP Rch Zn3 0.00...100.00 ohm 0.01 30.00 Minimum resistive
reach of PP/3P-
loops, zone 3
Max Ris PP Rch Zn3 0.00...100.00 ohm 0.01 30.00 Maximum resistive
reach of PP/3P-
loops, zone 3
PP operate delay
Zn3
20...60000 ms 1 20 Time delay to oper-
ate of PP/3P-loops,
zone 3
Op Mod Gnd loops
Zn3
0=False
1=True
0=False Enable PE-loop
measurement, zone
3
Gnd Op Dl mode
Zn3
0=False
1=True
1=True Enable operate tim-
er for PE-loops,
zone 3
Load Comp zone 3
0=False
1=True
1=True Enable load com-
pensation for PE-
loops, zone 3
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
989

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals