Parameter Values (Range) Unit Step Default Description
Par line Comp zone
1
0=False
1=True
0=False Enable parallel line
compensation for
PE-loops, zone 1
Mutual R0 zone 1 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
sistance, zone 1
Mutual X0 zone 1 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
actance, zone 1
Tilt angle zone 2 -45...45 deg 1 0 Tilt angle (posi-
tive value increases
zone area), zone 2
Par line Comp zone
2
0=False
1=True
0=False Enable parallel line
compensation for
PE-loops, zone 2
Mutual R0 zone 2 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
sistance, zone 2
Mutual X0 zone 2 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
actance, zone 2
Tilt angle zone 3 -45...45 deg 1 0 Tilt angle (posi-
tive value increases
zone area), zone 3
Par line Comp zone
3
0=False
1=True
0=False Enable parallel line
compensation for
PE-loops, zone 3
Mutual R0 zone 3 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
sistance, zone 3
Mutual X0 zone 3 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
actance, zone 3
Tilt angle zone 4 -45...45 deg 1 0 Tilt angle (posi-
tive value increases
zone area), zone 4
Par line Comp zone
4
0=False
1=True
0=False Enable parallel line
compensation for
PE-loops, zone 4
Mutual R0 zone 4 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
sistance, zone 4
Mutual X0 zone 4 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
actance, zone 4
Tilt angle zone 5 -45...45 deg 1 0 Tilt angle (posi-
tive value increases
zone area), zone 5
Par line Comp zone
5
0=False
1=True
0=False Enable parallel line
compensation for
PE-loops, zone 5
Mutual R0 zone 5 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
sistance, zone 5
Mutual X0 zone 5 0.00...3000.00 ohm 0.01 40.00 Parallel line zero se-
quence mutual re-
actance, zone 5
Table 930: DSTPDIS Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
993