Parameter Values (Range) Unit Step Default Description
Resistor pause 0...100000000 ms 1 5 Time between con-
secutive resistor
control sequence
repeats
Resonance curve
Cur
1=Icoil
2=Icoil + Ifix
2=Icoil + Ifix Resonance curve x-
axis title on HMI
Switch on delay 1 0...300000 ms 1 1000 Resistor switch-on
delay time
Time on 1 0...300000 ms 1 1000 Resistor switch on
time
Switch on delay 2 0...300000 ms 1 1000 Resistor repetition
switch-on delay
time
Time on 2 0...300000 ms 1 1000 Resistor repetition
switch-on time
Switch off delay 1 0...300000 ms 1 1000 Resistor switch-off
delay time
Time off 1 0...300000 ms 1 1000 Resistor switch-off
time
Switch off delay 2 0...300000 ms 1 1000 Resistor repetition
switch-off delay
time
Table 1595: PASANCR Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Tuning cycles 1...100 1 5 Maximum number
of tuning cycles
Tuning cycle delay 0...86400 s 1 300 Delay between con-
secutive tuning cy-
cles
Table 1596: PASANCR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Coil V Nom 0...400000 V 1 10000 Adjustable arc sup-
pression coil nomi-
nal voltage
Fix coil V Nom 0...400000 V 1 10000 Fixed arc suppres-
sion coil nominal
voltage
Auxiliary Wnd V
Nom
0...10000 V 1 500 Power auxiliary
winding nominal
voltage
Controller mode
0=Manual
1=Automatic
0=Manual Coil controller oper-
ating in automatic
or manual mode
Parallel resistor
0=False
1=True
0=False Parallel resistor in-
stallation status
R0Transformer 0...100 ohm 1 0 Zero-sequence re-
sistance of
the earthing/main
transformer
X0Transformer 0...100 ohm 1 0 Zero-sequence re-
actance of
the earthing/main
transformer
Voltage measure-
ment
1=Busbar
2=Coil
2=Coil Residual voltage
measurement from
busbar or from coil
Table continues on the next page