Parameter Values (Range) Unit Step Default Description
Position Meas
mode
1=Pos. indication
2=Pos. ind. and
meas.
1=Pos. indication Coil position meas-
urement mode
Resistor control
1=OFF
2=ON
3=Automatic
1=OFF Resistor control
mode
Resistor Nom value 0.00...100.00 ohm 0.01 5.00 Nominal resistance
of the parallel resis-
tor at power auxili-
ary winding secon-
dary voltage level
Coil losses 0.00...20.00 % 0.01 2.00 Coil losses
Fix coil value 0...10000 A 1 0 Inductive current
produced by fixed
coil at fixed coil
nominal voltage
level
Fix coil losses 0.00...20.00 % 0.01 2.00 Fix coil losses
Pot Max gap 0...100 % 1 5 Potentiometer
maximum gap
length
Fix coil type
1=OFF
2=ON
3=Automatic
1=OFF Fix coil type
Level detector op
0=Disable
1=Enable
1=Enable Enable / disable
level detector mod-
ule
Pot value 1 0...3000 ohm 1 0 Potentiometer val-
ue 1
Coil current 1 0...10000 A 1 0 Coil current 1
Pot value 2 0...3000 ohm 1 0 Potentiometer val-
ue 2
Coil current 2 0...10000 A 1 0 Coil current 2
Pot value 3 0...3000 ohm 1 0 Potentiometer val-
ue 3
Coil current 3 0...10000 A 1 0 Coil current 3
Pot value 4 0...3000 ohm 1 0 Potentiometer val-
ue 4
Coil current 4 0...10000 A 1 0 Coil current 4
Pot value 5 0...3000 ohm 1 0 Potentiometer val-
ue 5
Coil current 5 0...10000 A 1 0 Coil current 5
Pot value 6 0...3000 ohm 1 0 Potentiometer val-
ue 6
Coil current 6 0...10000 A 1 0 Coil current 6
Pot value 7 0...3000 ohm 1 0 Potentiometer val-
ue 7
Coil current 7 0...10000 A 1 0 Coil current 7
Pot value 8 0...3000 ohm 1 0 Potentiometer val-
ue 8
Coil current 8 0...10000 A 1 0 Coil current 8
Pot value 9 0...3000 ohm 1 0 Potentiometer val-
ue 9
Coil current 9 0...10000 A 1 0 Coil current 9
Pot value 10 0...3000 ohm 1 0 Potentiometer val-
ue 10
Coil current 10 0...10000 A 1 0 Coil current 10
Reset delay time EF 0...1000000 ms 1 500 Reset delay time
for earth-fault
Control functions 1MRS759142 F
1752 REX640
Technical Manual